ÃÛÌÒÓ°Ïñ

  PEMKO  

ASD030. CSI 3-Part Specifications.

INSTITUTIONAL SYSTEM 1 (CORRECTIONAL), SPECIFICATION

ASD030 Rev May 1995

SPECIFIER NOTE:

THE FOLLOWING DATA IS INTENDED TO ASSIST IN SPECIFYING PEMKO

PRODUCTS. INCORPORATE IN A PROJECT SPECIFICATION WHERE

APPROPRIATE.

CAREFULLY REVIEW TO ENSURE COORDINATION WITH ALL CONTRACT

DOCUMENTS.

1. PRODUCT: PEMKO INSTITUTIONAL SYSTEM No. 1 (CORRECTIONAL)

2. MANUFACTURER:

PEMKO * Ventura PEMKO * Memphis

4226 Transport Street 5535 Distribution Drive

Ventura, CA 93003 Memphis, TN 38141

Phone:(800) 283-9988 Phone (800) 824-3018

Fax: (800) 283-4050 Fax: (800) 243-3656

3. MATERIAL & FINISH:

SPECIFIER NOTE:

PRODUCT SELECTED IS AVAILABLE IN MATERIALS & FINISHES SPECIFIED

BELOW. WHERE MORE THAN ONE MATERIAL IS LISTED FOR A PRODUCT,

SELECT PARAGRAPH FOR MATERIAL YOU WANT.

EDIT BRACKETED TEXT TO SPECIFY FINISH. DELETE TEXT NOT DESIRED.

MATERIALS & FINISHES NOT LISTED MAY BE AVAILABLE BY SPECIAL

ORDER.

 

DOOR BOTTOM: PEMKO No. 18062CP

HOUSING:

Aluminum, Extruded

* Alloy Type 6063-T5

* Chemical and physical properties per the Aluminum

Association, Inc.

* Federal Specification QQ-A-200/9C.

* [18062CP, Clear Anodized; 18062DP, Dark Bronze

Anodized; 18062GP, Gold Anodized]

BRUSH:

* Nylon, Type 6, heat stabilized

PERIMETER GASKETING: PEMKO No. 45062CP

HOUSING:

Aluminum, Extruded

* Alloy Type 6063-T5

* Chemical and physical properties per the Aluminum

Association, Inc.

* Federal Specification QQ-A-200/9C.

* [45062CP, Clear Anodized; 45062DP, Dark Bronze

Anodized; 45062GP, Gold Anodized]

BRUSH:

* Nylon, Type 6, heat stabilized.

4.TEST & CODE COMPLIANCE:

Fire Label: Classified By UL For Application To Swinging

Type Fire Doors of the Hollow Metal or Steel

Covered composite type Rated up to 3 Hours, or

Wood Core Fire Doors rated up to 1-1/2

Hours Listed and Labeled as Gasketing

Materials. Tested in accordance with UL10B

by Underwriters Laboratory, Inc. .

Smoke Label: Smoke tested by WYLE Laboratories in

accordance with UL 1784-90; meets the

requirements of NFPA 105.

 

 

5.INSTALLATION:

Installation to be performed in strict accordance with

manufacturers instructions furnished with product.

Door Bottom: Cut to length equal to door width,crimp

ends of brush backing to retain bristles. Fasten to

bottom of door, locate screws in center of slots.

Adjust for proper contact with floor and tighten screws.

Perimeter Gasketing:Trim to length, crimp ends of brush

backing to retain bristles. Fasten to header first, then

jambs, ensure contact at threshold, hold lightly against

door and install screws in center of slots (drill metal

frame 7/64" or #36) Carefully miter or cope at corners

to ensure tight joints and continuous seal. Adjust as

required and tighten screws.

6 WARRANTY:

Guaranteed by manufacturer against defects in material

or workmanship for three years