ÃÛÌÒÓ°Ïñ

  PEMKO  

ASD032. CSI 3-Part Specifications.

INSTITUTIONAL SYSTEM 3, HOSPITAL SPECIFICATION ASD032 5-95

SPECIFIER NOTE:

THE FOLLOWING DATA IS INTENDED TO ASSIST IN SPECIFYING PEMKO

PRODUCTS. INCORPORATE IN A PROJECT SPECIFICATION WHERE

APPROPRIATE.

CAREFULLY REVIEW TO ENSURE COORDINATION WITH ALL CONTRACT

DOCUMENTS.

1. PRODUCT: PEMKO INSTITUTIONAL SYSTEM No. 3 (HOSPITAL)

2. MANUFACTURER:

PEMKO * Ventura PEMKO * Memphis

4226 Transport Street 5535 Distribution Drive

Ventura, CA 93003 Memphis, TN 38141

Phone:(800) 283-9988 Phone (800) 824-3018

Fax: (800) 283-4050 Fax: (800) 243-3656

3. MATERIAL & FINISH:

SPECIFIER NOTE:

PRODUCT SELECTED IS AVAILABLE IN MATERIALS & FINISHES SPECIFIED

BELOW. WHERE MORE THAN ONE MATERIAL IS LISTED FOR A PRODUCT,

SELECT PARAGRAPH FOR MATERIAL YOU WANT.

EDIT BRACKETED TEXT TO SPECIFY FINISH. DELETE TEXT NOT DESIRED.

MATERIALS & FINISHES NOT LISTED MAY BE AVAILABLE BY SPECIAL

ORDER.

.

AUTOMATIC DOOR BOTTOM: PEMKO No. 4301CPKL

CASE HOUSING:

Aluminum, Extruded

* Alloy Type 6063-T5

* Chemical and physical properties per the Aluminum

Association, Inc.

* Federal Specification QQ-A-200/9C.

* [4301BDGR, Bright Dip Gold Anodized; 4301CR, Clear

Anodized 4301DR, Dark Bronze Anodized]

SEAL:

PemkoPrene , Extruded thermoplastic elastomer

* Flexable between -70 F and +250 F

* Excellent flex fatigue

* Outstanding ozone resistance

PERIMETER GASKETING: PEMKO No.29310CP

HOUSING & SNAP-ON COVER

Aluminum, Extruded

* Alloy Type 6063-T5

* Chemical and physical properties per the Aluminum

Association, Inc.

* Federal Specification QQ-A-200/9C.

* [29310CP, Clear Anodized; 293D10P, Dark Bronze

Anodized; 29310GP, Gold Anodized]

SEAL:

Polyproplyene Pile

* AAMA Specification 701.2

4.TEST & CODE COMPLIANCE:

Fire Label: Classified By UL For Application To Swinging

Type Fire Doors of the Hollow Metal or Steel

Covered composite type Rated up to 3 Hours, or

Wood Core Fire Doors rated up to 1-1/2

Hours Listed and Labeled as Gasketing

Materials. Tested in accordance with UL10B

by Underwriters Laboratory, Inc. .

Smoke Label: Smoke tested by WYLE Laboratories in

accordance with UL 1784-90; meets the

requirements of NFPA 105.

5.INSTALLATION:

Installation to be performed in strict accordance with

manufacturers instructions furnished with product.

Automatic Door Bottom: Cut-down as required and fasten

to door. Adjust for proper contact with floor.

Perimeter Gasketing: NOTE: DO NOT INSTALL SNAP-ON COVERS

UNTIL FINAL ADJUSTMENT IS MADE AND SCREWS TIGHTENED

Fasten to header first, then jambs, ensure contact at

threshold, hold lightly against door and install screws

in center of slots (drill metal frame 7/64" or #36)

Carefully miter or cope at corners to ensure tight

joints and continuous seal. Adjust as required and

tighten screws. Snap on covers.

6 WARRANTY:

Guaranteed by manufacturer against defects in material

or workmanship for three years