M200 and M400 Smoke Curtains for Elevators
Other News Subscribe to FREE newsletter | Oct 03, 2017 |
In combination with the fire-rated doors used in nearly all elevators, the M200 Smoke Curtain provides comprehensive and code-compliant draft, smoke and fire control. This particular model is easy to install in nearly any environment and integrates seamlessly with existing fire protection systems to quickly bring a structure up to code.
Elevator hoistway opening sizes
42 inches and 48 inches only
Ceiling Height
Up to 10 feet high
Unit return sizes (projection from wall)
One inch
Housing dimensions
Housing width: 55 and 64 inches
Height: 10.5 inches Depth: 9 inches (plus return)
Unit electronic control
In electrical box mounted inside the housing
Emergency power source
No internal emergency power source.
Unit is fail safe and will deploy if primary power disrupted for several seconds.
Unit can be connected to emergency power.
Protection from temporary power failures
A brief delay avoids nuisance deploys.
Screen rewind switch
Yes, located on both sides of curtain
Screen deploy switch
Yes, located on controls inside housing
Stainless steel auxiliary rails
Yes, for all units. Rails can be painted to match in field.
Smoke Guard system (SGS) products are listed and labeled by Intertek (Omega Point Laboratories and ETL) in accordance with UL 1784 and UL 864 standards. Our systems are also recognized by the International Code Council (ICC) Evaluation Service, the California State Fire Marshal, and numerous state and local building jurisdictions. The Smoke Guard system exceeds the smoke containment standards prescribed in the International Building Code (IBC). See our Agency Approvals page for more information on our product listing and labeling.