About Tricon Copper
Tricon Copper
APPLICATION: Chilled Water, Condensate, Condenser Water, Domestic Water, Heating Hot Water, Potable Water, Process Piping Service Pipe: The service pipe shall be Type “K”, or Type “L” hard drawn seamless copper tubing to ASTM B-88 and WWT-799. Refrigerant piping shall meet ASTM B-280, Type ACR and ASME 31.5 Straight lengths of piping will be supplied in 20 ft. lengths with 6” of piping exposed at each end for field joint fabrication. Insulation:* The insulation shall be a foamed in place closed cell polyurethane which completely fills the annular space between the carrier pipe and the exterior casing. The insulation shall have the following physical properties: Exterior Casing:** The exterior casing shall be
(1) Seamless, extruded white PVC Type 1, Grade 1 Class 12454-B per ASTM D-1784 or
(2) High Density Polyethylene (H.D.P.E.) ASTM D-1248 with the following physical properties: No polyethylene tape casings will be allowed. Sub-Assemblies: All fittings, anchors, end seals, other accessories shall be prefabricated or field fabricated dependant upon engineer’s option and/or site conditions. Field Joints: After welding and hydrostatic testing, PVC jacketed straight field joints shall be insulated with polyurethane foam to the thickness specified, PVC sleeve and pressure sensitive tape. HDPE jackets will use polyurethane foam and a heat shrinkable sleeve. Expansion/Contraction Compensation: Expansion and contraction within the piping system shall be accommodated with factory prefabricated internal expansion elbows, z-bends, expansion loops, and anchors specifically designed for each application. External expansion compensation can be provided with the use of flexible foam bolsters. Installation: No Piping shall be installed in standing water. Trenches shall be maintained dry until final field closure is complete. The installing contractor shall handle the piping system in accordance with the directions furnished by the manufacturer and as approved by the architect and engineer. The service piping shall be hydrostatically tested to 1-1/2 times the operating pressure, or as specified in the contract documents. The test shall be maintained for a minimum time of 1 hour. EXERCISE DUE CARE WHEN INSTALLING AND TESTING THE PIPING SYSTEM. Backfill: A 4-inch layer of sand or fine gravel shall be placed and tamped in the trench to provide stable and uniform bedding for the piping system. Once the system is in place, the trenches shall be carefully backfilled and hand tamped in 6” layers until a cover of at least 24” from the top of the pipe has been achieved. The first 12” of backfill shall be sand or fine gravel less than ½” in diameter. The remainder of the backfill shall be void of rocks, frozen earth and foreign material over 2 ” in diameter. The trench shall be compacted to comply with H-20 Highway loading. Accessories: System Options: Contact your Tricon representative for available sizes and system options. Overview
SERVICE PIPE: Type "K" or "L" Hard Drawn Copper Tubing Conforming to ASTM B-88
INSULATION: Polyurethane Foam
JACKETING: HDPE / PVC / FRP / Galvanized / Stainless Steel / Aluminum
TEMP: Up to 250°F / 120°C
NOM. LENGTH: 20 Ft. System Specifications
Pipe Size
Minimal Insulation Thickness
PVC Jacket O.D.
PVC Jacket Wall
½”
1.88”
4.50”
.070”
¾”
1.74”
4.50”
.070”
1”
1.62”
4.50”
.070”
1¼”
1.50”
4.50”
.070”
1½”
1.37”
4.50”
.070”
2”
1.94”
6.14”
.070”
2½”
1.69”
6.14”
.070”
3”
1.44”
6.14”
.070”
4”
1.94”
8.16”
.080”
6”
1.94”
10.20”
.100”
Pipe Size
Minimal Insulation Thickness
HDPE Jacket O.D.
HDPE Jacket Wall
½”
1.79”
4.50”
.150”
¾”
1.66”
4.50”
.150”
1”
1.54”
4.50”
.150”
1¼”
1.41”
4.50”
.150”
1½”
1.29”
4.50”
.150”
2”
2.12”
6.63”
.150”
2½”
1.87”
6.63”
.150”
3”
1.62”
6.63”
.150”
4”
1.76”
8.00”
.150”
6”
1.76”
10.00”
.175”