APPLICATION: Steam, Condensate, High Temp. Hot Water, Process Piping
SERVICE PIPE: Carbon Steel
INSULATION: Cellular Glass & Polyurethane Foam, Calcium Silicate & Polyurethane Foam
JACKETING: HDPE / FRP / Galvanized / Stainless Steel / Aluminum
TEMP: Up to 366°F / 185 °C
NOM. LENGTH: 20 Ft. - 40 Ft.

System Specifications

Pipe Size Nominal Inner Insulation Thickness Nominal Outer Insulation Thickness HDPE Jacket O.D. System Temperature
2” 1½” 1.00” 8.00” 353°¹ó
2½” 2.00” 1.00” 10.00” 353°¹ó
3” 2.00” 1.00” 10.00” 353°¹ó
4” 2.50” 1.00” 12.43” 353°¹ó
6” 2.50” 1.00” 14.06” 353°¹ó
8” 2.50” 1.50” 17.83” 353°¹ó
10” 3.00” 1.50” 19.80” 353°¹ó
12” 3.00” 1.50” 22.17” 353°¹ó

Service Pipe:

Carbon steel service pipe shall be standard weight A53 ERW or A106 seamless beveled for welding. Condensate return piping shall be Schedule 80. All joints for pipe 2 ½” and larger in size shall be buttwelded. Sizes 2” and smaller shall be socket welded. Straight lengths of piping will be supplied with 6” of piping exposed at each end for field joint fabrication. Where possible, piping lengths shall be supplied in 40 Ft. random lengths.

Insulation: (Inner Layer)*

The inner layer of insulation will consist of cellular glass, calcium silicate or perlite.

Insulation: (Outer Layer)*

The outer conduit insulation shall be polyurethane foam with a minimum 1-inch thickness. The polyurethane foam shall have a minimum density of 2.0, and a closed cell content of 90% to 95% per ASTM D-2856, and shall have a “K” factor of .14 per ASTM C-177 @ 75° F.

Exterior Casing:**

The exterior casing shall be seamless, extruded High Density Polyethylene (H.D.P.E.) ASTM-1248, with the following physical properties:

  • ASTM D-3350…Resin Type III, Grade P34
  • ASTM D-638…Ultimate Elongation 850%
  • ASTM D-638…Tensile Yield Strength 3300 psi
  • ASTM D-790…Tangent Flexural Modules 175,000 psi

No polyethylene tape casings will be allowed.

Sub-Assemblies:

All fittings, anchors, and end seals, shall be factory fabricated and insulated. No field fabrication of fittings, anchors or end seals will be allowed.

Field Joints:

After welding and hydrostatic testing, all field joints shall be insulated with insulation materials as supplied by Tricon Piping Systems, Inc.

Expansion Compensation:

Expansion and contraction within the piping system shall be accommodated with factory-fabricated oversized elbows, z-bends, and loops.

Installation:

Trenches shall be maintained dry until final field closure is complete. Piping system not suitable for use in high water table.
The installing contractor shall handle the piping system in accordance with the directions furnished by the manufacturer and as approved by the architect and engineer. The service piping shall be hydrostatically tested to 1-1/2 times the operating pressure, or as specified in the contract documents. The test shall be maintained for a minimum time of 1 hour. EXERCISE DUE CARE WHEN INSTALLING AND TESTING THE PIPING SYSTEM.

Backfill:

A 4-inch layer of sand or fine gravel shall be placed and tamped in the trench to provide stable and uniform bedding for the piping system. Once the system is in place, the trenches shall be carefully backfilled and hand tamped in 6” layers until a cover of at least 24” from the top of the pipe has been achieved. The first 12” of backfill shall be sand or fine gravel less than ½” in diameter. The remainder of the backfill shall be void of rocks, frozen earth and foreign material over 6” in diameter. The trench shall be compacted to comply with H-20 Highway loading.

Accessories:

  • Heat Tracing

System Options:

  • *Insulation thickness will vary depending on the type of insulation specified and the operating temperature.
  • **Optional metallic casings for above ground applications include, Spiral Lockseam in Galvanized, Aluminum or Stainless Steel.
  • **Optional non-metallic casings for below grade offered include, Filament Wound FRP.

Contact your Tricon representative for available sizes and system options.

Brochures for Tricon Composite

Brochures for Tricon Composite
Preview Description Format Size Open
TriconComposite.pdf
Notice: This product literature and the recommendations for usage is intended for use by personnel having knowledge of industry accepted practice under normal operating conditions. Variations in environment, operating temperatures or extrapolation of data may cause unsatisfactory results. Tricon Piping Systems, Inc. recommends consulting your design engineer to verify the suitability of our products for your intended application. The information contained in this website is subject to change without notice.
PDF 1.9 MB Open
PHP  


Request for Information / Request a Catalog from Tricon Piping Systems, Inc. about Tricon Composite
 
(Please check companies and/or products above.)
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter ÃÛÌÒÓ°Ïñnews.  
     


News archive:
Tricon Composite Pipe System (Jul 28, 2023)
Tricon Composite (Jun 02, 2017)
Tricon Composite (Jan 11, 2016)
Featured Product: Tricon Composite (Feb 08, 2014)